Unbalanced Pressure Thrust · Anchor / Thrust-Block Sizing

Pipeline Thrust Calculator

Dead end: F = P·A₁  |  Tee branch: F = P·Ab
Bend: F = 2·P·A₁·sin(θ/2)

Area is estimated from the nominal diameter. Use "Custom diameter" for the actual bore or gasket seat diameter.

Thrust blocks are normally sized for the test pressure, not the operating pressure.

Only used for the tee row. Thrust acts along the branch axis: F = P·Ab (area of the branch, not the run).

Required anchor / thrust-block capacity = thrust × SF. A value of 1.5 is common.

Pressure P
Diameter D
Area A
Base force P·A
Bend thrust · resultant acts outward along the bisector θ = 90° → F = – kN
→ flow in flow out → F θ
90.0°
Thrust & required anchor force
Fitting / location Thrust F (kN) ≈ kgf Anchor ×SF (kN)
Pump nozzle check · unrestrained pressure thrust vs allowable flange load
SUCTION DISCHARGE
FlangeDNUnrestrained thrust P·A (kN) Allowable Fsum (kN)RatioVerdict
Enter the allowable flange load (vector sum Fsum) from the pump manufacturer's datasheet — ISO 5199 Annex B or API 610 tables — using the family-coefficient / material-adjusted values where applicable. The unrestrained thrust applies ONLY if an untied expansion joint / rubber bellows sits at the flange; with tied joints or rigid piping + anchors, P·A never reaches the nozzle and the check reverts to a piping stress analysis (weight + thermal) against the same allowables. Ratio 1.0–1.4 may be acceptable only via the ISO 5199 B.4.4 compensation formula (inlet + outlet combined ≤ 2). EJMA effective area of a bellows is 15–30% larger than the DN bore, so real bellows thrusts exceed the values shown.

Polarlys Innovation AS — water and wastewater engineering, Trondheim, Norway. Org. no. 820 776 402. [email protected]

Editorially independent. No supplier or product recommendations.

Provided for reference and preliminary take-off. Not a substitute for engineering design or a check against the governing standard. © Polarlys Innovation AS